JB-H(St)H Fire Alarm Electric Power Cable Wire Resistance Fire Rated Control Cable

Brand Name : Zion communication OR OEM

Model Number : JB

Certification : UL, ETL, CE,CPR, RoHS

Place of Origin : China

MOQ : 10 KM

Payment Terms : T/T, L/C

Supply Ability : 1000KM / Month

Delivery Time : 25 working days

Packaging Details : 100M, 300M, Wooden Reel, Carton

Conductor : Bare Copper, Solid

Insulation : LSZH T17

Identification : Colored DIN VDE 0815

Separator : Polyester Foil

Drain Wire : Tinned Copper, Solid

Shield : Aluminum/PET Foil

Contact Now

JB-H(St)H Fire Alarm Electric Power Cable Wire Resistance Fire Rated Control Cable
JB-H(St)H | J-H(St)H
Technical Data and Standards
Conductor: Bare Copper, Solid
Conductor standard: EN 60228 CI.1
Insulation: LSZH T17
Insulation Standard: DIN VDE 0207
Identification: Colored DIN VDE 0815
Separator: Polyester Foil
Drain Wire Tinned Copper, Solid
Shield: Aluminum/PET Foil
Out Jacket: LSZH M1

J- Installation Cable | B-Fire alarm | H-LSZH insulation | (St)-Electrostatic Screen | H-LSZH Jacket

LSZH: Thermoplastic Halogen-free compound T17

COMPLIANCE (Reference Standard and Certificates)
· Conductor: EN 60228 CI.1 | Insulation: EN 50363-7 | Jacket: EN50363-8
· Fire behaviour: IEC 60332.3/EN 60332-3
· Halogen free: IEC 60574.1/EN50267-2-1 | Low Smoke emission: EN61034.2

JB-H(St)H Fire Alarm Electric Power Cable Wire Resistance Fire Rated Control Cable


Application Support
· These cables are designed for signal transmission in fire detection systems.
· For fixed installation on and under plaster,in dry and damp rooms
but also in the open air for fixed installation on outer walls of buildings.
· Suitable for installation in public buildings (hospitals, theatres, ecc.).
Technical Data of conductor
Diameter(mm) 0,80 1,00 1,13 1,50
Section(mm²) 0,50 0,80 1,00 1,80
Cond. Resistance (ohm/km) 34,50 22,00 17,20 9,80
Cond. Loop Res.(ohm/km) 69,00 44,00 34,40 19,60
Electrical Characteristics
Peak Operating Voltage 300 V
Operating Voltage Uo 500 V
Test Voltage 800 V
Insulation Resistance 100M ohm/km
PHYSICAL PROPERTIES
Bend Radius(Min) 10×OD of Jacket
Operating Temperature -15 to 70
Construction
Item Inner Conductor Insulation Shield Jacket
Cores OD
(mm)
Section
(mm²)
OD
(mm)
Color OD
(mm)
JBHSH0102080 1×2 0,80 0,50 1,55 R/B PET Foil
Drain Wire
AL/PET Foil
4,30
JBHSH0104080 1×4 0,80 0,50 1,55 R/B/W/Y 5,10
JBHSH0202080 2×2 0,80 0,50 1,55 R/B/W/Y 6,50
JBHSH01020100 1×2 1,00 0,80 1,90 R/B 5,20
JBHSH0102113 1×2 1,13 1,00 45.0 R/B 5,60
JBHSH0102150 1×2 1,50 1,80 42.0 R/B 7,40
R:RED B:BLACK W:WHITE Y:YELLOW
Tolerance range for insulation and sheath diameter. Insulation: ±0,05mm | Jacket:±0,30 mm
Order Informations
Marking HELLOSIGNAL JB-H(ST)H N×N×N Fire alarm Cable ...300M(or Per customer's request)
Inner Package 300m/Spool(or Per customer's request)
Outer Package Carton, Pallet (or Per customer's request)
Delivery time Normally 25 days after received the deposit.
Brand HELLOSIGNAL® OR OEM

Product Tags:

LSZH T17 Fire Rated Control Cable

      

Wire Resistance Fireproof Electrical Cable

      
Quality JB-H(St)H Fire Alarm Electric Power Cable Wire Resistance Fire Rated Control Cable wholesale